Annual backflow device testing and certification
The yearly test of a testable backflow device in Melbourne: which devices need it, who may test them, what the test costs and what happens when one fails.
Every testable backflow prevention device on a Melbourne property must be tested at least once every 12 months, and the result has to reach the water corporation that supplies the site. The test is done in place, at the meter, by a plumber who holds the specialised backflow prevention class with the Building and Plumbing Commission (BPC). This site passes your request to an independent licensed provider, and that provider quotes, tests and signs the report.

Which devices need a yearly test?
A backflow device stops water inside a property from running back into the public main when pressure drops or when on-site pressure is higher than the main. The device is chosen by hazard rating, and only the testable types carry the annual duty. The definitions below come from the containment guidelines adopted by Melbourne’s water corporations.
| Device | Hazard rating | Testable | Where it is usually found |
|---|---|---|---|
| Reduced pressure zone device (RPZD) | High: could cause death | Yes | Main meter of sites that store or dose chemicals, plus standpipes |
| Double check valve | Medium: could endanger health | Yes | Main meter of many shops, offices, workshops and strata blocks |
| Testable single check valve or detector assembly | Low, used on fire services | Yes | Fire hydrant and sprinkler services |
| Dual check valve | Low: a nuisance only | No | Many domestic meter assemblies |
| Registered air gap or break tank | High | Registered, checked at least yearly | Process water and high hazard plant |
Greater Western Water says devices are required on medium and high risk properties such as commercial and industrial sites, and also on homes with a bidet, a toilet douche or a below ground rainwater tank. So the annual test is not only a factory issue. Check your water corporation’s backflow page if you are unsure whether a device on your meter is on their register.
Who is allowed to do the test?
Under Part 5 of the Plumbing Regulations 2018, backflow prevention work means the repair, alteration, maintenance, testing or commissioning of a testable device listed in AS/NZS 3500.1. The BPC page on backflow prevention work sets the entry bar: the plumber must already be registered or licensed in water supply work, must have completed the unit CPCPWT4022 (Commission and maintain backflow prevention devices) and must pass the BPC exam for the class. A plumber licensed only in water supply work can install a device but cannot commission it or sign off the annual test.
Before you book anyone, search the plumber’s name or licence number on the BPC practitioner register and confirm that backflow prevention appears among their classes.
What happens on the day?
The tester finds the device, records its make, size and serial number, and checks the check valves and, on an RPZD, the relief valve against the procedures in AS/NZS 2845.3. Test cocks on the device let the gauge read pressure differences without cutting into pipework. The supply through the device has to be isolated while it is checked, so ask how long the water will be off and tell tenants or staff before the visit. A pass is recorded on the report. A fail means the device needs servicing or replacement and then a fresh test.
Give the tester clear access. Devices in Melbourne sit in meter cages on the front boundary, in basement plant rooms of apartment towers, and inside locked compounds at industrial sites. If the tester arrives and nobody has the cage key, expect the return visit to be charged.
What does an annual test cost?
A published Melbourne cost table puts the first device on a site at $150 to $320 per device, and each extra device tested at the same visit at $90 to $145 per device. On a site with a drinking water device and a fire service device, the second one falls under the additional device line in that table. The Melbourne backflow cost guide explains what moves the price and what a quote should include, such as travel, lodgement and any after hours loading.
When is the report due?
Each corporation sets its own deadline. Greater Western Water asks for the completed inspection and maintenance form within 14 days of the test. The guidelines Yarra Valley Water adopted allow 20 days. South East Water sends a yearly reminder and takes reports through its backflow team. Our page on test report lodgement and water corporation notices sets out each one and what to do if a reminder letter has already arrived.
What if the device fails?
A failed device is a repair job, not a paperwork problem. South East Water’s fact sheet for business customers expects a failed device to be repaired within 20 business days. The backflow valve repairs page covers kit replacement, whole device replacement and the retest that has to follow.
What a careful tester will not do
- Sign a report for a device they did not test, or copy last year’s readings.
- Use a test kit with no current calibration record. The corporations’ report forms ask for the kit serial number and calibration date.
- Remove, bypass or blank off a device to restore pressure. The guidelines list bypassing without the corporation’s authority as grounds for disconnection.
- Swap a double check valve for a lower rated device because it is cheaper. Any change in hazard needs a written reassessment sent to the corporation.
The Melbourne angle
Three retail water corporations cover metropolitan Melbourne: Greater Western Water in the CBD and the west, Yarra Valley Water across the north and east, and South East Water in the south east. The device register, the reminder letter and the report address all depend on which one supplies your meter. The Melbourne CBD page covers high rise plant rooms, the Dandenong page covers the industrial south east, and the Sunshine page covers the west. If the site also has a hydrant or sprinkler service, read about fire service backflow testing before booking, so both devices are tested in one visit.
What to do next
Find the meter number, count the devices, note their sizes and the date of the last test, and photograph any reminder letter. Then request an annual backflow test with those details so a licensed tester can quote for the right number of devices.
Frequently asked questions
- How often does a backflow device need testing?
Every testable device on the register needs a test at least once in each 12 month period. The guidelines adopted by Melbourne's water corporations say the interval must be no more than 12 months, counted from when the device was first commissioned.
- How long does an annual backflow test take?
It depends on the site. Time on site grows with the number of devices, locked plant rooms, fire service isolation and any repairs found. Ask the provider for an estimate of how long the supply will be off.
- Can I test my own backflow device?
No, unless you hold the backflow prevention class yourself. Testing a testable device is defined as backflow prevention work under the plumbing regulations, and the report has to carry the tester's licence or registration number.
- Will the water be turned off during the test?
The section of supply running through the device is isolated while each valve is checked. Plan for a short interruption and warn tenants, residents or staff beforehand. Sites that cannot lose water during trading can ask for an early or late booking.
- What happens if my device fails the test?
The tester records the fail and should explain which valve failed. The device then needs servicing or replacing, followed by a fresh test, before a passing result can be sent to the corporation. South East Water, for example, expects failed devices to be fixed within 20 business days.