Fire service backflow testing
Annual testing of the backflow device on a hydrant or sprinkler service in Melbourne: which device is needed, who may test it and how to plan the shutdown.
Most commercial and industrial properties in Melbourne, and some larger residential buildings, have a fire service from the water main, and that service needs its own backflow device at the boundary. Where the device is testable, it goes on the water corporation’s register and must be tested every year like any drinking water device. Enquiries here are passed to independent providers licensed in backflow prevention, who quote and test the fire service device and can often do the drinking water device on the same visit.

Why does a fire service need backflow protection?
Water sitting in hydrant and sprinkler pipework can stand for months, and some systems can be fed by a fire brigade pumper, a tank or a booster. Without a device, that water could be pushed or drawn back into the public main. Yarra Valley Water describes fire services as privately owned and maintained assets that include all pipework into the property, apart from the corporation’s stop valve on the main and the meter. The owner pays for the device, its maintenance and its yearly test.
Which device does a fire service need?
The containment guidelines adopted by Melbourne’s water corporations set a floor and then step up with the risk.
| Fire service situation | Minimum device in the guidelines |
|---|---|
| Any fire service | A low hazard containment device |
| Hydrant or sprinkler service of 80mm or more | A testable single check valve as a minimum |
| Service using an alternative water source or chemical additive | A higher hazard device |
| Booster connection within 180m of an open water source such as a river or dam | A higher hazard device |
| Fire equipment inside a high hazard area | Protection matched to that hazard |
South East Water says most industrial and commercial properties need a containment device on both the drinking water supply and the fire service. Its backflow page names testable fire service single check valves among the devices that must be tested at least once a year by a licensed plumber endorsed for backflow prevention testing. Read the South East Water backflow requirements for the forms it asks plumbers to use.
Which licence covers the work?
Two BPC plumbing classes meet at a fire service. Testing, commissioning and repairing a testable backflow device is backflow prevention work. Work on the rest of the fire service, from the connection to the supply up to the hydrants and sprinklers, is fire protection work under Part 4 of the Plumbing Regulations 2018, with NCC Volume Three among its compliance requirements. Some providers hold both classes. If yours holds only the backflow class, they test the device and the fire services contractor looks after everything downstream. Check both on the BPC register when one business claims to do it all.
Planning the test
Isolating a fire service is not like turning off a garden tap. Before the test day:
- Tell the building’s fire services contractor and the alarm monitoring company the date and the expected time the service will be isolated.
- Agree who will restore the service and confirm it is back in operation before the tester leaves.
- Arrange access to the valve pit or plant room, which may be in a locked enclosure on the street boundary or in a basement car park.
- Check whether the drinking water device on the same site is due, so both are tested in one visit.
Yarra Valley Water bills the water that passes through a fire service meter, including water used for testing, so a test that drains a large main can show on the next bill.
Shared fire and drinking water services
Yarra Valley Water says some smaller sites have both fire and drinking water supplied through a single shared pipeline and meter. Then the device at the meter protects both, and it must suit the higher of the two hazards. On those sites there is no second device to find: the one at the meter does both jobs.
What does fire service backflow testing cost?
The published Melbourne cost table gives no separate figure for fire service tests. Its general lines are $150 to $320 per device for one device, and $90 to $145 per device for each further device checked during that visit. Large fire service valves take longer, and coordination with the fire contractor can add time. For a new or replacement RPZD on a 25 to 32mm commercial or fire service, the same table gives $1,250 to $3,200. Larger fire mains cost more again. See the backflow testing cost guide for how to compare quotes.
What a careful provider will not do
- Isolate a fire service without warning the people who monitor it.
- Leave the service isolated overnight to come back and finish.
- Fit a lower rated device than the corporation requires to reduce pressure loss.
- Lodge a fire service report under the drinking water device’s details.
Local angle
Yarra Valley Water says fire services are required on most industrial and commercial properties, which takes in much of the factory land in Campbellfield and Dandenong and the office towers of the CBD. If a failed fire service check valve needs replacing, the repair and replacement page covers the options, and annual testing explains the drinking water side.
What to do next
Note the size of the fire service, the device make if visible, the name of the fire services contractor and the monitoring company. Then request a fire service backflow test and say whether the drinking water device should be tested at the same time.
Frequently asked questions
- Does a fire sprinkler or hydrant service need a backflow device?
Yes. The containment guidelines used by Melbourne's corporations require at least a low hazard device on every fire service, and a testable single check valve on hydrant and sprinkler services of 80mm and above. Services with chemical additives or alternative water sources need a higher rated device.
- Who should test the backflow device on a fire service?
A plumber with the backflow prevention class tests the device. The rest of the fire service falls under fire protection work, a separate plumbing class. Some providers hold both, and if not, the backflow tester works alongside the fire services contractor.
- Will testing set off the fire alarm or affect insurance?
Isolating a fire service can trigger valve monitoring and leaves the building without that protection during the test. Notify the monitoring company and the fire contractor first, and ask the provider to restore and confirm the service before leaving. Ask your insurer if your policy sets any conditions.
- Can the fire service and drinking water devices be tested on the same visit?
Yes, and it is usually cheaper, because the second device is priced as an additional device rather than a new call-out. Make sure each device gets its own report so the corporation records both.